Device Type
                                
                                
                                    24 VDC Solenoid coils
                                
                             
                            
                                
                                    ON-State Output rating
                                
                                
                                    500 mA continuous @ 24 VDC. The power is derived from power supplied to the CHARMs Smart Logic Solver Carrier
                                
                             
                            
                                
                                    ON-State Current Limit
                                
                                
                                    Output inrush current limited to 1.16 A
                                
                             
                            
                                
                                    OFF-State Leakage Current
                                
                                
                                    5 mA maximum.
                                
                             
                            
                                
                                    Line Fault Detection Levels
                                
                                
                                    Guaranteed Short Circuit: <10 Ω Load, Guaranteed Good Status: 56 Ω to 3.5 kΩ Load, Guaranteed Open Circuit: > 20 kΩ Load
                                
                             
                            
                                
                                    Line Fault Test Timing
                                
                                
                                    200 µsec
                                
                             
                            
                                
                                    Field Circuit Protection
                                
                                
                                    1.16 A Current Limiting Circuit, Field wiring disconnect
                                
                             
                            
                                
                                    Field Power Common Shutoff Signal
                                
                                
                                    Logic low removes field power like in de-energize to trip applications
                                
                             
                            
                                
                                    CHARM Power req.
                                
                                
                                    82 mA max.(109 mA when used with Relay Terminal block) @ 24 VDC
                                
                             
                            
                                
                                    CHARM Heat Dissipation
                                
                                
                                    2.6 W