Communication Protocol
                                
                                
                                    Optional HART™ communications on the 0-20 mA analog current (FSK) - used for maintenance, configuration changes and asset management, available in mA source output wiring options. RS-485 Modbus compatible communication link that can be used in computer controlled installations
                                
                             
                            
                                
                                    Ambient Temperature
                                
                                
                                    Operating: -76 °F to +185 °F (-60 °C to +85 °C)
Storage: -76 °F to +185 °F (-60 °C to +85 °C)
                                
                             
                            
                                
                                    Enclosure Rating
                                
                                
                                    Stainless Steel 316L with electro polish finish
Heavy duty copper free aluminum (less than 1%), polyurethane painted
                                
                             
                            
                                
                                    Mounting
                                
                                
                                    Stainless Steel 316L with electro polish finish
                                
                             
                            
                                
                                    Dimensions
                                
                                
                                    Detector 4"x 4.6"x 6.18"(101.6 x 117 x 157 mm)
                                
                             
                            
                                
                                    Weight
                                
                                
                                    Detector (stainless steel 316L) 6.3 lb (2.9 kg)
Detector (aluminum) 2.8 lb (1.3 kg)
Tilt mount 2.5 lb (1.1 kg)
                                
                             
                            
                                
                                    Certifications/Approvals
                                
                                
                                    ATEX and IECEx:
- Ex II 2 G D
- Ex db eb op is IIC T4 Gb
- Ex tb op is IIIC T110 °C Db
- (Ta -50°C to +85°C) IP66/68
FM/FMC
- Class I, Division 1, Groups B, C, and D, T4A
- Class II, III, Division 1, Groups E, F, and G, T4A
- Class I, Division 2, Groups A, B, C, and D, T4
- Ta = -50°C to +85°C
- Type 6P, IP66/68 2 m for 45 minutes
CSA/US:
- Class I, Division 1, Groups B, C, and D, T4 
- Class II, III, Division 1, Groups E, F, and G, T4 
- Class I, Division 2, Groups A, B, C, and D, T4 
- Ta = -50 °C to +85 °C 
- Type 6P; IP 66/68 2 m for 45 minutes 
TR CU (EAC):
- 1 Ex db eb op is IIC T4 Gb X
- Ex tb op is IIIC T110°C Db X
- (–55°C Ta +85°C)
Performance:
Reliability:
- Designed to meet IEC 61508 - SIL 3 (TÜV)
Marine: